Datasheet excerpt: Technical data of  NBN40-L2-E2-V1-3G-3D

General specifications
Switching functionNormally open (NO)
Output typePNP
Rated operating distance40 mm
Installationnon-flush
Output polarityDC
Assured operating distance0 ... 32.4 mm
Actual operating distance36 ... 44 mm typ. 40 mm
Reduction factor rAl0.33
Reduction factor rCu0.31
Reduction factor r3040.74
Reduction factor rBrass0.38
Output type3-wire
Nominal ratings
Operating voltage10 ... 30 V DC
Switching frequency0 ... 180 Hz
Hysteresistyp. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionpulsing
Voltage drop≤ 2 V
Operating current0 ... 200 mA
Off-state current0 ... 0.5 mA
No-load supply current≤ 20 mA
Time delay before availability80 ms
Operating voltage indicatorLED, green
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd1057 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity

StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
IECEx approval

Equipment protection level Gc (ec)IECEx TUR 21.0019X

Equipment protection level Dc (tc)IECEx TUR 21.0020X
ATEX approval

Equipment protection level Gc (ec)TÜV 20 ATEX 8525 X

Equipment protection level Dc (tc)TÜV 20 ATEX 8526 X
UL approvalcULus Listed, General Purpose
Marine approvalDNVGL TAA0000160
Ambient conditions
Ambient temperature-25 ... 85 °C (-13 ... 185 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection typeConnector plug M12 x 1 , 4-pin
Housing materialPA
Sensing facePA
Degree of protectionIP69K
Cable

Cable diameter3.3 mm ± 0.15 mm
Mass130 g
Dimensions

Height40 mm

Width40 mm

Length67 mm
General information
Use in the hazardous areasee instruction manuals