M12*78 Plug in High Pressure Inductive Proximity Sensor equivalent to BES 516-100-S45-S4-D (BHS0001)
| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | NAMUR | |
| Slot width | 5 mm | |
| Depth of immersion (lateral) | 5 ... 7 mm , typ. 6 mm | |
| Output type | 2-wire | |
| Nominal ratings | ||
| Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | |
| Operating voltage | 5 ... 25 V | |
| Switching frequency | 0 ... 2000 Hz | |
| Hysteresis | 0.05 ... 0.65 mm | |
| Current consumption | ||
| Measuring plate not detected | ≥ 3 mA at nominal voltage | |
| Measuring plate detected | ≤ 1 mA at nominal voltage | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| MTTFd | 9060 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Compliance with standards and directives | ||
| Standard conformity | ||
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
| Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 | |
| Approvals and certificates | ||
| IECEx approval | ||
| Equipment protection level Ga | IECEx PTB 11.0091X | |
| Equipment protection level Gb | IECEx PTB 11.0091X | |
| Equipment protection level Da | IECEx PTB 11.0091X | |
| Equipment protection level Mb | IECEx PTB 11.0091X | |
| ATEX approval | ||
| Equipment protection level Ga | PTB 99 ATEX 2219 X | |
| Equipment protection level Gb | PTB 99 ATEX 2219 X | |
| Equipment protection level Da | PTB 99 ATEX 2219 X | |
| UL approval | cULus Listed, General Purpose | |
| Ordinary Location | E87056 | |
| Hazardous Location | E501628 | |
| Control drawing | 116-0453 | |
| CCC approval | ||
| Hazardous Location | 2020322315002306 | |
| NEPSI approval | ||
| NEPSI certificate | GYJ16.1391X | |
| TIIS approval | on request | |
| KCC approval | ||
| Hazardous Location | 13-AV4BO-0353X | |
| Marine approval | DNVGL TAA00001A5 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
| Mechanical specifications | ||
| Connection type | flexible leads LiY | |
| Housing material | PBT | |
| Degree of protection | IP67 | |
| Cable | ||
| Cable diameter | 1.1 mm ± 0.1 mm | |
| Bending radius | > 10 x cable diameter | |
| Material | PVC | |
| Core cross section | 0.14 mm2 | |
| Length | 500 mm | |
| Dimensions | ||
| Height | 15 mm | |
| Width | 10 mm | |
| Length | 15 mm | |
| General information | ||
| Use in the hazardous area | see instruction manuals | |