5 mm flush Temperature range -40 ... 150 °C (-40 ... 302 °F)
B站不支持收货地址
B站不支持库存规格
Trade Terms
FOB
Payment Terms
TT
Delivery Time
7-10 days
Packing
Polybag/box
Shipping
By sea, By air or By express delivery (DHL/UPS/FEDEX/TNT/EMS)
MOQ
1
Place of Origin
China
Certificate
CE,ROHS,UL
参数暂无数据
多属性暂无数据
B站不支持优惠卷
暂无分享
B站不支持产品保障

Datasheet excerpt: Technical data of  NJ5-18GK-N-150

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance5 mm
Installationflush
Assured operating distance0 ... 4.05 mm
Reduction factor rAl0.4
Reduction factor rCu0.3
Reduction factor r3040.85
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Switching frequency0 ... 500 Hz
Current consumption

Measuring plate not detectedmin. 3 mA

Measuring plate detected≤ 1 mA
Functional safety related parameters
MTTFd4542 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity

NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999

StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
IECEx approval

Equipment protection level GaIECEx PTB 11.0037X

Equipment protection level GbIECEx PTB 11.0037X

Equipment protection level DaIECEx PTB 11.0037X

Equipment protection level MbIECEx PTB 11.0037X
ATEX approval

Equipment protection level GaPTB 00 ATEX 2048 X

Equipment protection level GbPTB 00 ATEX 2048 X

Equipment protection level DaPTB 00 ATEX 2048 X
UL approval

Ordinary LocationE87056

Hazardous LocationE501628

Control drawing116-0452
CCC approval

Hazardous Location2020322315002257
NEPSI approval

NEPSI certificateGYJ16.1393X
CML approvalon request
ANZEx18.3018X
Ambient conditions
Ambient temperature-40 ... 150 °C (-40 ... 302 °F)
Mechanical specifications
Connection typecable
Housing materialPPS
Sensing facePPS
Degree of protectionIP65
Cable

Cable diameter4.8 mm ± 0.2 mm

Bending radius> 10 x cable diameter

MaterialSIHF

Core cross section0.34 mm2

Length2 m
Dimensions

Length47 mm

Diameter18 mm
General information
Use in the hazardous areasee instruction manuals


Product Message